Steel Tee Support Design Mar 2019

Consider a widely used pipe support structure — the tee support
Let’s just start with a basic design:

the tee is 8′ tall (bottom of base plate to top of steel beam)
the tee beam is 4′ wide
the steel column and beam are W8x31 (A992)
Tee 3D
Tee Lengths
This size tee is one of the most sturdy that we will design.

any shorter and we would have used a W6x15 column and beam,
any taller or wider and the deflections under load would be larger
Now let’s document the BCs, the unit load deflections and the resulting k-factors

Axes and Boundary Conditions (BCs)
Y is vertical
The tee is in the YZ plane
X is out of plane and
X is the longitudinal axis of the supported pipe
The column base of the tee is fixed
Loading and Deflections
Givens:

One kip load in each axis direction
Load point is at end point of the tee beam (2′ out from CL column)

X axis deflection = 2.39″; k-factor = 0.42 kips per inch (mostly beam rotation)
Y axis deflection = 0.03″; k-factor = 33.3 kips per inch
Z axis deflection = 0.12″; k-factor = 8.33 kips per inch
Notice the very low stiffness in response to lateral load Fx
This is because the wide flange column has relatively small torsional stiffness
Givens:

One kip load in each axis direction
Load point is at intersection of tee column and beam

X axis deflection = 0.34″; k-factor = 2.94 kips per inch
Y axis deflection = 0.00″; k-factor = say ‘rigid’
Z axis deflection = 0.12″; k-factor = 8.33 kips per inch
Suggested Loading
Minimum suggested pipe loadings for the tee:

consider future loading, future add-ons, and abuse
tributary length: use at least 20′ (even if the spacing is less)
tributary width: use at least the beam width (consider future)
use at least 40 psf gravity load (DL + FL) over the tributary area
use a friction coefficient, mu (μ), of at least 40%
few lines on a tee; therefore, take no benefit for opposing friction loadings

use joint load Fx (LL) at end of beam of at least 0.5 kip
use joint load Fz (LL) at CL of beam of at least 0.5 kip

account for control stations, valves, etc

wind load basis: Fz (WL) at CL of beam
wind load basis: use at least largest diameter pipe + 10% of rack width
wind load basis: consider pipe insulation
wind load basis: use Cf of at least 0.70

Other loadings for the tee:

account for electrical/instrument (E/I) equipment
~~~